User Tools

Site Tools


en:datasheets:smarthub

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
en:datasheets:smarthub [2024-08-06 12:03] – [Application] jes_alexaueren:datasheets:smarthub [2024-08-07 18:39] (current) – [Advantanges] jesadmin
Line 1: Line 1:
 ~~NOTOC~~ ~~NOTOC~~
 +[[this>doku.php?id=en:datasheets:smarthub&do=export_pdf&tpl=datasheet_en&book_title=JES smart/HUB Data Sheet|PDF]]
  
 {{ :media:smarthub:smarthub-d2_perspective1.png?400 |}} {{ :media:smarthub:smarthub-d2_perspective1.png?400 |}}
Line 11: Line 12:
 ===== Features ===== ===== Features =====
  
- +  * Connects one or multiple JES or 3rd party sensors to an IP network 
-  * Smart, IoT data acquisition and recording device (data logger) +  * Integration into the JES smart/Architecture 
-  * DIN rail housing for easy instal lation +  * IoT enabled 
-  * Optional touch LCD display visible in the housing cover +  * DIN rail mount 
-  * Integrated Web Server +  * Standard interfaces on base unit 
-    * Visualization of recorded data +    * MODBUS RTU (RS-485) 
-    * Export of data +    * MODBUS/TCP (Ethernet) 
-    * configuration +    * Web service (Ethernet) 
-  * 1 x Ethernet port +  * Additional interface options (implemented on request) 
-    * JSON +    * MQTT 
-    * MODBUS/TCP +    * OPC UA 
-    * Connection to smart/CONTROL Server +    * NTCIP 
-  * 1 x RS-485 galvanically isolated +  * Inputs and outputs on smart/HUB 
-    * MODBUS RTU +    * 1 x Ethernet 
-  * 2 x Digital input +    * 1 x USB 
-  * 2 x Relay output (changer) +    * 1 x RS485 
-  * 1 x HDMI for connecting the optional 7" touch display +    * 2 x digital input 
-  * Expansion modules connected via bus connectors integrated in the DIN rail+    * 2 x relay output 
 +    * 1 x HDMI 
 +  * DIN rail extension modules 
     * 4 x RS-485 galvanically isolated     * 4 x RS-485 galvanically isolated
-    * 4 x Analog Input*+  Optional integrated 2.4" touch display (Configuration code D2) 
 +  Optional external 7" smart/CORE-D7 touch display 
  
-* planned, but will only be implemented in the case of an order 
 ===== System ===== ===== System =====
  
-  * smart/HUB IoT data acquisition device for DIN rail mounting +  * smart/HUB IoT gateway, data logger and control unit for DIN rail mounting 
-  * Optionalsmart/HUB-SD2 Sensor Display for displaying status and current measured values +  * Optional smart/HUB-D2 Sensor Display for displaying status and current measured values 
-  * Optionalsmart/HUB-D7 7" touch display connected via HDMI+  * Optional smart/HUB-D7 7" touch display connected via HDMI 
 +  * Optional DIN rail modules with additional functionalities connected via bus connectors in DIN rail
  
  
Line 49: Line 54:
 Different interfaces are available on the base unit or via extensions for connecting the sensors. Extensions are connected to the base unit via a bus connector integrated into the DIN rail. Different interfaces are available on the base unit or via extensions for connecting the sensors. Extensions are connected to the base unit via a bus connector integrated into the DIN rail.
  
-The base unit reads the data from sensors from various manufacturers via sensor specific plugins and records them. Protocols such as MODBUS RTU, MODBUS ASCII, Lufft UMB*, 1-wire as well as 4-20 mA analog inputs and digital inputs are supported as standard. Additional plugins can be implemented at any time.+The base unit reads the data from sensors from various manufacturers via sensor-specific plugins and records them. Protocols such as MODBUS RTU, MODBUS ASCII, Lufft UMB*, 1-wire as well as 4-20 mA analog inputs and digital inputs are supported as standard. Additional plugins can be implemented at any time.
  
 smart/HUB can be expanded into a universal operator panel with a 7" touch display. smart/HUB can be expanded into a universal operator panel with a 7" touch display.
  
-smart/HUB is part of the JES smart/architecture and serves both as an operator panel and as an IoT gateway for sensors without an Ethernet connection. The smart/architecture also includes smart/sensors and smart/CONTROL, a sensor control center for collecting and visualizing all sensor data, central user administration, sensor monitoring, and maintenance control and documentation.+smart/HUB is part of the JES smart/architecture and serves both as an operator panel and as an IoT gateway for sensors without an Ethernet connection. The smart/Architecture also includes smart/sensors and smart/CONTROL, a sensor control center for collecting and visualising all sensor data, central user administration, sensor monitoring, and maintenance control and documentation.
  
-smart/HUB can be used wherever data from sensors from different manufacturers is to be collected and administered in a uniform form in one platform, e.road weather stations, tunnel sensors.+smart/HUB can be used wherever data from sensors from different manufacturers is to be collected and administered in a uniform form in one platform, e.g. road weather stations, tunnel sensors.
  
  
 ===== Advantanges ===== ===== Advantanges =====
  
-  * Specially developed for use in traffic engineering+  * Specially developed for use in transport infrastructure
   * Condition monitoring   * Condition monitoring
   * Central administration   * Central administration
   * Remote maintenance   * Remote maintenance
-  * Flexible integration into technology+  * Flexible integration into existing environment
  
 <newcolumn> <newcolumn>
 ===== Application ===== ===== Application =====
  
-Tunnels are important infrastructure elements in road networks that facilitate connections between regions. The environmental conditions prevailing therein are influenced by smoke, fog, dust and exhaust gases and should be monitored so as not to expose people to dangers and impairments as they pass through. Fires in particular have had dramatic consequences in the past. At all times, people in the tunnel must be supplied with sufficient breathing air and suitable visibility conditions must be ensured. 
  
-Since 1990JES Elektrotechnik GmbH has been developinginstalling and maintaining systems for monitoring air quality and lighting conditions in tunnels. Our systems are robust, durable and resistant to the corrosive tunnel atmosphere and work reliably and preciselyThey comply with the requirements of Directive 2004/54/EC (minimum safety requirements for tunnels in the trans European road network) and the more precise national directives and regulations+~~SNIPPET_O1752352293~~en:snippets:datasheet:application~~ 
-  * Austria: RVS 09.02 Tunnel Equipment +Tunnels are important infrastructure elements in road networks and facilitate the connection of regions.  
-  * Germany: RABT guidelines for the equipment and operation of road tunnels + 
-  * Switzerland: FEDRO Guidelines and Technical Manual of Operating and Safety Equipment (BSA)+Environmental conditions in tunnels are influenced by fog, particles and emissions and need to be monitored to protect people on their passage through the tunnel from danger and impacts on their health. Accidents in tunnels, and particularly fires, can have dramatic consequences and can prove extremely costly in terms of human life, increased congestion, pollution and repair costs. At every time people in the tunnel need to be supplied with breathable air and sufficient visibility. 
 + 
 +Since 1990 JES Elektrotechnik GmbH developsinstalls and maintains systems to monitor air characteristics and lighting conditions in tunnels. Our systems are robust, durable and resistant against the corrosive atmosphere in a tunnel. They operate reliably and have a high accuracy in measurement 
 + 
 +All systems fulfil the requirements of the EC guideline 2004/54/EC (Minimum safety requirements for tunnels in the trans-European road network) and the more detailed national guidelines and provisions: 
 + 
 +  * Austria: RVS 09.02 Tunnelausrüstung 
 +  * Germany: RABT Richtlinien für die Ausstattung und den Betrieb von Straßentunneln 
 +  * Switzerland: ASTRA Richtlinien und Fachhandbuch Betriebs- und Sicherheitsausrüstungen (BSA) 
 + 
 +Our range of products for tunnel covers systems for monitoring of
  
-Our product range in the field of tunnel safety includes systems for measuring: +  * Visibility (extractive or in-situ)  
-  * Toxic gases such as CO, NO, NO<sub>2</sub>, etc. (extractive or in-situ) +  * Toxic gases like CO, NO, NO<sub>2</sub> (extractive or in-situ) 
-  * Visual opacity (extractive or in-situ) +  * Air velocity, direction and temperature 
-  * Airvelocity,direction and temperature +  * Luminance (accessthreshold and interior zone)
-  * Luminance (approach pathin-sight section, transition section, inner section)+
   * Illuminance   * Illuminance
 +~~SNIPPET_C~~en:snippets:datasheet:application~~
  
  
Line 93: Line 107:
  
  
-~~SNIPPET_O1722945796~~en:snippets:techdata:hub:hub~~+ 
 {|class="techdata" {|class="techdata"
 !colspan="3"|IoT gateway, data logger and control unit smart/HUB !colspan="3"|IoT gateway, data logger and control unit smart/HUB
Line 144: Line 159:
  
 |} |}
-~~SNIPPET_C~~en:snippets:techdata:hub:hub~~ 
  
  
Line 153: Line 167:
  
  
-~~SNIPPET_O1722945796~~en:snippets:techdata:hub:hub-d2~~+~~SNIPPET_O1752352293~~en:snippets:techdata:hub:hub-d2~~
 {|class="techdata" {|class="techdata"
 !colspan="3"|IoT gateway, data logger and control unit smart/HUB-D2 !colspan="3"|IoT gateway, data logger and control unit smart/HUB-D2
Line 222: Line 236:
  
  
-~~SNIPPET_O1722945796~~en:snippets:techdata:hub:hub-485~~+~~SNIPPET_O1752352293~~en:snippets:techdata:hub:hub-485~~
 {|class="techdata" {|class="techdata"
 !colspan="2"|4 x RS-485 extension !colspan="2"|4 x RS-485 extension
Line 264: Line 278:
  
  
-~~SNIPPET_O1722945796~~en:snippets:techdata:core:core-d7~~+~~SNIPPET_O1752352293~~en:snippets:techdata:core:core-d7~~
 {|class="techdata" {|class="techdata"
 !colspan="3"|7" External touch display smart/CORE-D7 !colspan="3"|7" External touch display smart/CORE-D7
Line 320: Line 334:
 ~~SNIPPET_C~~en:snippets:techdata:core:core-d7~~ ~~SNIPPET_C~~en:snippets:techdata:core:core-d7~~
  
 +==== Conformities ====
 +
 +
 +~~SNIPPET_O1752352293~~en:snippets:techdata:hub:hub_conformities~~
 +{|class="techdata"
 +!colspan="2"|Conformities
 +|-
 +|Markings
 +|{{:media:common:ce_logo.png?50|}}  {{:media:common:ccsaus_mark_transparent.png?50|}}
 +|-
 +|Electrical standards
 +|2014/35/EU Low Voltage Directive (LVD) \\
 +2014/30/EU Electromagnetic compatibility (EMC) \\
 +EN IEC 61000-6-2:2019 Immunity standard for industrial environments \\
 +EN IEC 61000-6-3:2007 + A1: 2011 Emission standard for residential, commercial and light-industrial environments \\
 +EN 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use \\
 +EN 61326-1 Electrical equipment for measurement, control and laboratory use - EMC requirements
 +|}
 +~~SNIPPET_C~~en:snippets:techdata:hub:hub_conformities~~
  
en/datasheets/smarthub.1722945796.txt.gz · Last modified: by jes_alexauer