| - | ====== JES t/FL-USP Air Flow Sensor ====== | + | ====== JES t/ |
| <columns 100% 33% 33% -> | <columns 100% 33% 33% -> | ||
| ===== Features ===== | ===== Features ===== | ||
| + | *Precise ultrasonic air flow measuring system based on different transition times of ul-trasonic pulses | ||
| + | *Measurement of airflow at a single point | ||
| + | *Connection to tunnel control system either via analogue outputs or via RS 485 ASCII | ||
| + | *Optional, remote smart/HUB touch operating unit to | ||
| + | *display measured values | ||
| + | *modify parameters | ||
| + | *additional outputs | ||
| - | *Precise ultrasonic air flow measuring system based on different transition times of ultrasonic pulses | ||
| - | *Measurement of average air-flow over the whole tunnel cross section | ||
| - | *Sensor setup via service interface | ||
| - | *Suitable for tunnel cross sections up to 18 m \\ (Measuring path up to 25 m) | ||
| - | *Connection to tunnel control system either via analogue output and relays or via RS 485 MODBUS RTU | ||
| - | *Visible LEDs to indicate sensor status | ||
| - | *Optional, remote smart/HUB touch operation unit to display measured values and to modify parameters | ||
| ===== System setup ===== | ===== System setup ===== | ||
| - | | + | |
| - | *Terminal box for master to connect the power supply | + | |
| - | *Terminal box for Slave | + | *t/ |
| - | *Optional | + | *Alternative smart/ |
| + | *Optional smart/HUB touch operating unit | ||
| < | < | ||
| Line 29: | Line 31: | ||
| ===== Operation ===== | ===== Operation ===== | ||
| - | The air flow monitoring system measures the air flow based on different transmission times of ultrasonic pulses sent in one or the other direction. | + | The air flow monitoring system measures the air flow based on different transmission times of ultrasonic pulses sent in one or the other direction. |
| + | |||
| + | The arms of this single point air flow sensor are directed in the longitudinal axis of the tunnel. Ultrasonic pulses are exchanged between the two sensor arms. | ||
| - | Two sensors are mounted below the tunnel | + | Air flow in the tunnel |
| - | Air flow in the tunnel influences the transition time of the pulses be-tween sender | + | Measured values are air speed, air flow rate, direction |
| - | Measured values are air speed, air flow rate, direction of air flow and air temperature. | ||
| ===== Advantanges ===== | ===== Advantanges ===== | ||
| Line 74: | Line 77: | ||
| </ | </ | ||
| - | |||
| - | {{ : | ||
| < | < | ||
| Line 81: | Line 82: | ||
| ===== Technical Specifications ===== | ===== Technical Specifications ===== | ||
| - | |||
| - | ~~SNIPPET_O1709070954~~en: | ||
| + | ~~SNIPPET_O1762481951~~en: | ||
| {|class=" | {|class=" | ||
| - | !colspan=" | + | !colspan=" |
| |- | |- | ||
| |Type | |Type | ||
| - | |JES t/FL-USX | + | |colspan=" |
| |- | |- | ||
| |Measuring method | |Measuring method | ||
| - | |Determination of direction dependant differential | + | |colspan=" |
| |- | |- | ||
| - | |Measured values | + | |Measured values |
| - | |Air speed \\ Air flow rate \\ Direction of air flow \\ Air temperature | + | |Air velocity |
| + | | 0 .. 75 m/s \\ 1° or 181° \\ -50 .. 70 °C | ||
| + | |0.1 m/s \\ n/a \\ 0.1 °C | ||
| |- | |- | ||
| - | |Measuring range | + | |Accuracy |
| - | | -40 .. 40 m/s | + | |colspan=" |
| - | |- | + | |
| - | |Resolution | + | |
| - | |0.1 m/s, accuracy depending on measuring distance, flow profile, installation, | + | |
| - | |- | + | |
| - | |Response time | + | |
| - | |> 1s … 180 s, configurable | + | |
| - | |- | + | |
| - | |Measurement path length | + | |
| - | |1.2 - 25 m | + | |
| |- | |- | ||
| |Alignment | |Alignment | ||
| - | |30 - 60° to tunnel longitudinal axis, typically 45° | + | |colspan=" |
| |} | |} | ||
| - | + | ~~SNIPPET_C~~en: | |
| - | ~~SNIPPET_C~~en: | + | |
| - | + | ||
| - | + | ||
| - | + | ||
| - | ~~SNIPPET_O1709070972~~en: | + | |
| + | ~~SNIPPET_O1762481951~~en: | ||
| {|class=" | {|class=" | ||
| !colspan=" | !colspan=" | ||
| + | |- | ||
| + | |Digital interface | ||
| + | |1 x RS-485 MODBUS ASCII with different telegrams | ||
| |- | |- | ||
| |Analogue output | |Analogue output | ||
| - | |1 x 4-20 mA, 400 Ω, isolated \\ can be assigned any measured value and output range | + | |2 x 4-20 mA, max. 400 Ω, assignable to air velocity, direction or acoustic-virtual temperature |
| |- | |- | ||
| |Output range | |Output range | ||
| - | |configurable, | + | |configurable, |
| - | |- | + | |
| - | |Relay contacts | + | |
| - | |1 x fault indication (NC) \\ 1 x direction of air flow (NC) \\ (max. 48 V / 0.5 A) | + | |
| - | |- | + | |
| - | |Digital interfaces | + | |
| - | |1x RS 485 MODBUS RTU to control system, bidirectional \\ 1x Intercom RS 485 master-slave | + | |
| |} | |} | ||
| + | ~~SNIPPET_C~~en: | ||
| - | ~~SNIPPET_C~~en: | + | ==== Ultrasonic sensor ==== |
| - | < | + | ~~SNIPPET_O1762481951~~en: |
| - | ==== Ultrasonic transceiver (sensor) ==== | + | |
| - | + | ||
| - | + | ||
| - | ~~SNIPPET_O1709155386~~en: | + | |
| {|class=" | {|class=" | ||
| - | !colspan=" | + | !colspan=" |
| |- | |- | ||
| |Type | |Type | ||
| - | |DURAG D-FL 220T M | + | |JES t/FL-USP-USS |
| - | |rowspan=" | + | |rowspan=" |
| |- | |- | ||
| |Operating voltage | |Operating voltage | ||
| - | |24 VDC ± 10 % | + | |8 .. 42 VDC or \\ 12 .. 28V AC |
| |- | |- | ||
| - | |Current | + | |Power consumption |
| - | |1 A | + | |typ. 1.5 VA, max. 2.5 VA |
| + | |- | ||
| + | |Heating | ||
| + | |24 VAC/DC ± 15 %; typ. 45VA, max. 60VA @ 24V | ||
| |- | |- | ||
| |Appliance class | |Appliance class | ||
| |Class III | |Class III | ||
| - | |- | ||
| - | |Service interface | ||
| - | |USB 1.1 | ||
| - | |- | ||
| - | |MTBF | ||
| - | |> 170.000 h within service life if used within specifications | ||
| |- | |- | ||
| |Material | |Material | ||
| - | |Sensor housing: Polyamide RAL5017, Flammability rating: B1 (UL 94 V0) \\ Wall bracket: | + | |Stainless steel 1.4404 (AISI 316L) |
| |- | |- | ||
| |IP rating | |IP rating | ||
| - | |IP 69 | + | |IP 67 |
| |- | |- | ||
| |Dimensions | |Dimensions | ||
| - | |270 x 130 x 95 mm | + | |422 x 287 mm |
| |- | |- | ||
| |Weight | |Weight | ||
| - | |Sensor 2.2 kg \\ Wall bracket 1.6 kg | + | |Sensor 2.5 kg |
| |- | |- | ||
| |Indoor/ | |Indoor/ | ||
| Line 184: | Line 164: | ||
| |- | |- | ||
| |Temperature range | |Temperature range | ||
| - | | -40 .. +70 °C | + | | -50 .. 80 °C (heated) \\ -30 .. 80 °C (unheated) |
| |- | |- | ||
| |Humidity range | |Humidity range | ||
| Line 193: | Line 173: | ||
| |} | |} | ||
| - | ~~SNIPPET_C~~en: | + | ~~SNIPPET_C~~en: |
| < | < | ||
| - | ==== t/FL-USX-TBX terminal boxes ==== | + | ==== t/FL-USP-TBX Terminal box ==== |
| - | ~~SNIPPET_O1709155386~~en: | + | ~~SNIPPET_O1762481951~~en: |
| {|class=" | {|class=" | ||
| - | !colspan=" | + | !colspan=" |
| |- | |- | ||
| |Type | |Type | ||
| - | |t/FL-USX-TBX-A | + | |t/FL-USP-TBX |
| |rowspan=" | |rowspan=" | ||
| |- | |- | ||
| |System cable port | |System cable port | ||
| - | |1 (for D-FL 220 T M Sensor | + | |1 (for t/FL-USP Sensor) |
| |- | |- | ||
| |Power supply | |Power supply | ||
| Line 258: | Line 239: | ||
| |} | |} | ||
| - | ~~SNIPPET_C~~en: | + | ~~SNIPPET_C~~en: |
| + | ==== smart/ | ||
| - | ~~SNIPPET_O1709155386~~en: | + | ~~SNIPPET_O1762481951~~en: |
| {|class=" | {|class=" | ||
| - | !colspan=" | + | !colspan=" |
| |- | |- | ||
| |Type | |Type | ||
| - | |t/ | + | |smart/ |
| - | |rowspan=" | + | |
| - | |- | + | |
| - | |System cable port | + | |
| - | |1 (for D-FL 220 T M Sensor B) | + | |
| - | |- | + | |
| - | |Power supply | + | |
| - | |24 VDC ±10 % | + | |
| - | |- | + | |
| - | |Current rating | + | |
| - | |1 A | + | |
| - | |- | + | |
| - | |Appliance class | + | |
| - | |Class III | + | |
| - | |- | + | |
| - | |Material | + | |
| - | |Stainless steel 1.4404 (AISI 316L) | + | |
| - | |- | + | |
| - | |Mounting | + | |
| - | |incl. mounting clamp made from Stainless steel 1.4404 for wall mounting | + | |
| - | |- | + | |
| - | |IP rating | + | |
| - | |IP 69 | + | |
| - | |- | + | |
| - | |Dimensions | + | |
| - | |160 x 160 x 110 mm | + | |
| - | |- | + | |
| - | |Weight | + | |
| - | |approx. 1.9 kg | + | |
| - | |- | + | |
| - | |Indoor/ | + | |
| - | |Indoor use (tunnel) | + | |
| - | |- | + | |
| - | |Temperature range | + | |
| - | | -40 .. +60 °C | + | |
| - | |- | + | |
| - | |Humidity range | + | |
| - | |0 .. 100% relative humidity (non-condensing) | + | |
| - | |- | + | |
| - | |Pollution degree | + | |
| - | |4 (intended environment) / 2 (when cover removed) | + | |
| - | + | ||
| - | |} | + | |
| - | ~~SNIPPET_C~~en: | + | |
| - | + | ||
| - | + | ||
| - | < | + | |
| - | + | ||
| - | ==== smart/ | + | |
| - | + | ||
| - | + | ||
| - | ~~SNIPPET_O1709155386~~en: | + | |
| - | {|class=" | + | |
| - | !colspan=" | + | |
| - | |- | + | |
| - | |Type | + | |
| - | |smart/ | + | |
| |rowspan=" | |rowspan=" | ||
| |- | |- | ||
| |System cable port | |System cable port | ||
| - | |1 (for D-FL 220 T M sensor) | + | |1 (for t/FL-USP Sensor) |
| |- | |- | ||
| |Power supply | |Power supply | ||
| Line 380: | Line 306: | ||
| |} | |} | ||
| - | ~~SNIPPET_C~~en: | + | ~~SNIPPET_C~~en: |
| + | ==== Conformities ==== | ||
| - | ==== Conformities ==== | + | ~~SNIPPET_O1762481951~~en: |
| - | + | ||
| - | ~~SNIPPET_O1709155386~~en: | + | |
| {|class=" | {|class=" | ||
| !colspan=" | !colspan=" | ||
| |- | |- | ||
| |Markings | |Markings | ||
| - | |{{: | + | |{{: |
| |- | |- | ||
| |Electrical standards | |Electrical standards | ||
| - | |2014/35/EU Low Voltage Directive | + | |2014/35/EU Low voltage directive |
| - | 2014/30/EU Electromagnetic compatibility (EMC) \\ | + | |
| - | EN 61010-1 Safety requirements for electrical equipment for measurement, | + | |
| - | EN 61326-1 Electrical equipment | + | |
| |- | |- | ||
| |Tunnel safety standards | |Tunnel safety standards | ||
| - | |AT: RVS 09.02.22 \\ | + | |Austria: RVS 09.02.22 \\ |
| - | DE: RABT 2006 \\ | + | Germany: RABT 2006 \\ |
| - | CH: ASTRA RL 13001, Fachhandbuch BSA \\ | + | Switzerland: ASTRA RL 13001, Fachhandbuch BSA \\ |
| - | NO: Norwegian Public Roads Administration Handbook No. 021 Road Tunnels | + | Norway: Norwegian Public Roads Administration Handbook No. 021 Road Tunnels |
| + | International: | ||
| |} | |} | ||