 +[[this>doku.php?id=en:datasheets:tfl-usp&do=export_pdf&tpl=datasheet_en&book_title=JES t/FL-USP Data Sheet|PDF]]
  
 {{ :media:tfl-usp:4.3865.0x.xxx.png?173 | t/FL-USP Air Flow Sensor}} {{ :media:tfl-usp:4.3865.0x.xxx.png?173 | t/FL-USP Air Flow Sensor}}
Line 5: Line 6:
 <pagebreak> <pagebreak>
  
-====== JES t/FL-USP Air Flow Sensor ======+====== JES t/FL-USP Ultrasonic Point Air Flow Sensor ======
  
 <columns 100% 33% 33% -> <columns 100% 33% 33% ->
Line 20: Line 21:
  
 ===== System setup ===== ===== System setup =====
 +
   *Single sensor for wall-mounting with system cable   *Single sensor for wall-mounting with system cable
   *t/FL-USP-TBX Terminal box for analogue and RS-485 connections   *t/FL-USP-TBX Terminal box for analogue and RS-485 connections
Line 75: Line 77:
  
 </columns> </columns>
- 
-{{ :media:tfl-usx:fl-usx_grafik_2015-08-05.png?nolink&600 |}} 
  
 <pagebreak> <pagebreak>
Line 82: Line 82:
 ===== Technical Specifications ===== ===== Technical Specifications =====
  
- 
-~~SNIPPET_O1709070954~~en:snippets:techdata:tfl-usx:tfl-usx_airflow-measurement~~ 
  
  
 +~~SNIPPET_O1752335525~~en:snippets:techdata:tfl-usp:tfl-usp_airflow-measurement~~
 {|class="techdata" {|class="techdata"
-!colspan="2"|Air flow measurement+!colspan="4"|Air flow measurement
 |- |-
 |Type  |Type 
-|JES t/FL-USX+|colspan="3"|JES t/FL-USP
 |- |-
 |Measuring method |Measuring method
-|Determination of direction dependant differential transi-tion times of ultrasonic pulses+|colspan="3"|Determination of direction dependant differential transition times of ultrasonic pulses
 |- |-
-|Measured values +|Measured values / ranges / resolution 
-|Air speed \\ Air flow rate \\ Direction of air flow \\ Air temperature+|Air velocity \\ Direction of air flow \\ Acoustic-virtual temperature 
 +| 0 .. 75 m/s \\ 1° or 181° \\ -50 .. 70 °C 
 +|0.1 m/s \\ n/a \\ 0.1 °C
 |- |-
-|Measuring range  +|Accuracy 
--40 .. 40 m/s +|colspan="3"|≤ 5 m/s: ± 0.1 m/s (rmsmean over 360°) \\ > 5 m/s: ± 2 % (rmsmean over 360°)
-|- +
-|Resolution  +
-|0.1 m/s, accuracy depending on measuring distance, flow profile, installation, typically <±0.2 m/s at 3 m/s +
-|- +
-|Response time +
-|> 1s … 180 sconfigurable +
-|- +
-|Measurement path length +
-|1.2 - 25 m+
 |- |-
 |Alignment |Alignment
-|30 - 60° to tunnel longitudinal axis, typically 45°+|colspan="3"|in tunnel longitudinal axis
 |} |}
- +~~SNIPPET_C~~en:snippets:techdata:tfl-usp:tfl-usp_airflow-measurement~~
-~~SNIPPET_C~~en:snippets:techdata:tfl-usx:tfl-usx_airflow-measurement~~ +
- +
- +
- +
-~~SNIPPET_O1709070972~~en:snippets:techdata:tfl-usx:tfl-usx_outputs~~+
  
  
 +~~SNIPPET_O1752335525~~en:snippets:techdata:tfl-usp:tfl-usp_outputs~~
 {|class="techdata" {|class="techdata"
 !colspan="2"|Outputs !colspan="2"|Outputs
 +|-
 +|Digital interface 
 +|1 x RS-485 MODBUS ASCII with different telegrams
 |- |-
 |Analogue output |Analogue output
-|x 4-20 mA, 400 Ω, isolated \\ can be assigned any measured value and output range+|x 4-20 mA, max. 400 Ω, assignable to air velocity, direction or acoustic-virtual temperature
 |- |-
 |Output range |Output range
-|configurable, typically: -20 to 20 m/s +|configurable, typically: -20 to 20 m/s for air velocity
-|- +
-|Relay contacts +
-|1 x fault indication (NC) \\ 1 x direction of air flow (NC) \\ (max. 48 V / 0.5 A) +
-|- +
-|Digital interfaces  +
-|1x RS 485 MODBUS RTU to control system, bidirectional \\ 1x Intercom RS 485 master-slave+
 |} |}
 +~~SNIPPET_C~~en:snippets:techdata:tfl-usp:tfl-usp_outputs~~
  
-~~SNIPPET_C~~en:snippets:techdata:tfl-usx:tfl-usx_outputs~~ +==== Ultrasonic sensor ====
- +
-<pagebreak> +
-==== Ultrasonic transceiver (sensor==== +
  
-~~SNIPPET_O1709155386~~en:snippets:techdata:tfl-usx:d-fl220tm~~+~~SNIPPET_O1752335525~~en:snippets:techdata:tfl-usp:tfl-usp-uss~~
 {|class="techdata" {|class="techdata"
-!colspan="3"|Sensor +!colspan="3"|Ultrasonic Sensor 
 |- |-
 |Type  |Type 
-|DURAG D-FL 220T M +|JES t/FL-USP-USS 
-|rowspan="15" class="image"|{{:media:tfl-usx:d-fl220t.png?200|}}+|rowspan="15" class="image"|{{:media:tfl-usp:4.3865.0x.xxx.png?173|}}
 |- |-
 |Operating voltage |Operating voltage
-|24 VDC ± 10 %+|8 .. 42 VDC or \\ 12 .. 28V AC
 |- |-
-|Current consumption +|Power consumption 
-|1 A+|typ. 1.5 VA, max. 2.5 VA 
 +|- 
 +|Heating 
 +|24 VAC/DC ± 15 %; typ. 45VA, max. 60VA @ 24V
 |- |-
 |Appliance class  |Appliance class 
 |Class III |Class III
-|- 
-|Service interface 
-|USB 1.1 
-|- 
-|MTBF 
-|> 170.000 h within service life if used within specifications 
 |- |-
 |Material  |Material 
-|Sensor housing: Polyamide RAL5017, Flammability rating: B1 (UL 94 V0) \\ Wall bracket: Stainless steel 1.4404 (AISI 316L) or 1.4571 (AISI 316Ti)+|Stainless steel 1.4404 (AISI 316L) 
 |- |-
 |IP rating  |IP rating 
-|IP 69+|IP 67
 |- |-
 |Dimensions  |Dimensions 
-|270 130 x 95 mm+|422 287 mm
 |- |-
 |Weight  |Weight 
-|Sensor 2.2 kg \\ Wall bracket 1.6 kg+|Sensor 2.kg
 |- |-
 |Indoor/Outdoor use  |Indoor/Outdoor use 
Line 185: Line 164:
 |- |-
 |Temperature range  |Temperature range 
-| -40 .. +70 °C+| -50 .. 80 °C (heated) \\ -30 .. 80 °C (unheated)
 |- |-
 |Humidity range  |Humidity range 
Line 194: Line 173:
  
 |} |}
-~~SNIPPET_C~~en:snippets:techdata:tfl-usx:d-fl220tm~~+~~SNIPPET_C~~en:snippets:techdata:tfl-usp:tfl-usp-uss~~ 
  
  
 <pagebreak> <pagebreak>
  
-==== t/FL-USX-TBX terminal boxes ====+==== t/FL-USP-TBX Terminal box ====
  
  
-~~SNIPPET_O1709155386~~en:snippets:techdata:tfl-usx:tfl-usx-tbx-a~~+~~SNIPPET_O1752335525~~en:snippets:techdata:tfl-usp:tfl-usp-tbx~~
 {|class="techdata" {|class="techdata"
-!colspan="3"|Terminal box A - JES t/FL-USX-TBX-A+!colspan="3"|Terminal box t/FL-USP-TBX
 |- |-
 |Type  |Type 
-|t/FL-USX-TBX-A+|t/FL-USP-TBX
 |rowspan="17" class="image"|{{media:tfl-usx:430007-00_t-fl-usx-tbx-a-blank-std_asm_front2.png?nolink&200|}} |rowspan="17" class="image"|{{media:tfl-usx:430007-00_t-fl-usx-tbx-a-blank-std_asm_front2.png?nolink&200|}}
 |- |-
 |System cable port |System cable port
-|1 (for D-FL 220 T M Sensor A)+|1 (for t/FL-USP Sensor)
 |- |-
 |Power supply  |Power supply 
Line 259: Line 239:
  
 |} |}
-~~SNIPPET_C~~en:snippets:techdata:tfl-usx:tfl-usx-tbx-a~~+~~SNIPPET_C~~en:snippets:techdata:tfl-usp:tfl-usp-tbx~~
  
  
 +==== smart/BOX-S-FL-USP gateway (instead of t/FL-USP-TBX for Ethernet connection) ====
  
  
  
-~~SNIPPET_O1709155386~~en:snippets:techdata:tfl-usx:tfl-usx-tbx-b~~+~~SNIPPET_O1752335525~~en:snippets:techdata:tfl-usp:smartbox-s-fl-usp~~
 {|class="techdata" {|class="techdata"
-!colspan="3"|Terminal box B - t/FL-USX-TBX-B+!colspan="3"|smart/Architecture gateway for t/FL-USP smart/BOX-S-FL-USP
 |- |-
 |Type  |Type 
-|t/FL-USX-TBX-B +|smart/BOX-S-FL-USP
-|rowspan="14" class="image"|{{media:tfl-usx:430009-00_t-fl-usx-tbx-b-blank-std_asm_front1.png?nolink&150|}} +
-|- +
-|System cable port +
-|1 (for D-FL 220 T M Sensor B) +
-|- +
-|Power supply  +
-|24 VDC ±10 % +
-|- +
-|Current rating +
-|1 A +
-|- +
-|Appliance class  +
-|Class III +
-|- +
-|Material  +
-|Stainless steel 1.4404 (AISI 316L)  +
-|- +
-|Mounting +
-|incl. mounting clamp made from Stainless steel 1.4404 for wall mounting +
-|- +
-|IP rating  +
-|IP 69  +
-|- +
-|Dimensions  +
-|160 x 160 x 110 mm +
-|- +
-|Weight  +
-|approx. 1.9 kg +
-|- +
-|Indoor/Outdoor use  +
-|Indoor use (tunnel) +
-|- +
-|Temperature range  +
-| -40 .. +60 °C +
-|- +
-|Humidity range  +
-|0 .. 100% relative humidity (non-condensing)  +
-|- +
-|Pollution degree +
-|4 (intended environment) / 2 (when cover removed) +
- +
-|} +
-~~SNIPPET_C~~en:snippets:techdata:tfl-usx:tfl-usx-tbx-b~~ +
- +
- +
-<pagebreak> +
- +
-==== smart/BOX-S-FL-USX gateway (instead of t/FL-USX-TBX-A for Ethernet connection) ==== +
- +
- +
-~~SNIPPET_O1709155386~~en:snippets:techdata:tfl-usx:smartbox-s-fl-usx~~ +
-{|class="techdata" +
-!colspan="3"|smart/Architecture gateway for t/FL-USX - smart/BOX-S-FL-USX +
-|- +
-|Type  +
-|smart/BOX-S-FL-USX+
 |rowspan="18" class="image"|{{media:tfl-usx:430007-00_t-fl-usx-tbx-a-blank-std_asm_front2.png?nolink&200|}} |rowspan="18" class="image"|{{media:tfl-usx:430007-00_t-fl-usx-tbx-a-blank-std_asm_front2.png?nolink&200|}}
 |- |-
 |System cable port |System cable port
-|1 (for D-FL 220 T M sensor)+|1 (for t/FL-USP Sensor)
 |- |-
 |Power supply  |Power supply 
Line 381: Line 306:
  
 |} |}
-~~SNIPPET_C~~en:snippets:techdata:tfl-usx:smartbox-s-fl-usx~~+~~SNIPPET_C~~en:snippets:techdata:tfl-usp:smartbox-s-fl-usp~~
  
 +==== Conformities ====
  
  
-==== Conformities ==== +~~SNIPPET_O1752335525~~en:snippets:techdata:tfl-usp:tfl-usp_conformities~~
- +
-~~SNIPPET_O1709155386~~en:snippets:techdata:tfl-usx:tfl-usx_conformities~~+
 {|class="techdata" {|class="techdata"
 !colspan="2"|Conformities !colspan="2"|Conformities
 |- |-
 |Markings |Markings
-|{{:media:common:ce_logo.png?50|}}  {{:media:common:ccsaus_mark_transparent.png?50|}}+|{{:media:common:ce_logo.png?50|}}  
 |- |-
 |Electrical standards |Electrical standards
-|2014/35/EU Low Voltage Directive (LVD) \\ +|2014/35/EU Low voltage directive (LVD) \\ 2014/30/EU Electromagnetic compatibility (EMC) \\ 2011/65/EU RoHS 1 directive 2012/19/EU WEEE Directive \\ EN IEC 61000-6-2:2019 Immunity standard for industrial environments \\ EN IEC 61000-6-3:2007 + A1: 2011 Emission standard for residential, commercial and light-industrial environments \\ EN 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use \\ EN IEC 63000:2019-05 Technical documentation for the assessment of electrical and electronic products with respect to the restriction of hazardous substances
-2014/30/EU Electromagnetic compatibility (EMC) \\ +
-EN 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use \\ +
-EN 61326-1 Electrical equipment for measurement, control and laboratory use - EMC requirements+
 |- |-
 |Tunnel safety standards |Tunnel safety standards
-|AT: RVS 09.02.22 \\ +|Austria: RVS 09.02.22 \\ 
-DE: RABT 2006 \\ +Germany: RABT 2006 \\ 
-CH: ASTRA RL 13001, Fachhandbuch BSA \\ +Switzerland: ASTRA RL 13001, Fachhandbuch BSA \\ 
-NO: Norwegian Public Roads Administration Handbook No. 021 Road Tunnels+Norway: Norwegian Public Roads Administration Handbook No. 021 Road Tunnels \\ 
 +International: ISO 23431 Measurement of road tunnel air quality
 |} |}
-~~SNIPPET_C~~en:snippets:techdata:tfl-usx:tfl-usx_conformities~~+~~SNIPPET_C~~en:snippets:techdata:tfl-usp:tfl-usp_conformities~~
  
en/datasheets/tfl-usp.1711485758.txt.gz · Last modified: by jesadmin