JES smart/HUB Operating Unit
Features
* planned, but will only be implemented in the case of an order System
|
Operationsmart/HUB is a universal operating unit for collecting, storing or forwarding sensor data in IP networks to a server. Different interfaces are available on the base unit or via extensions for connecting the sensors. Extensions are connected to the base unit via a bus connector integrated into the DIN rail. The base unit reads the data from sensors from various manufacturers via sensor specific plugins and records them. Protocols such as MODBUS RTU, MODBUS ASCII, Lufft UMB*, 1-wire as well as 4-20 mA analog inputs and digital inputs are supported as standard. Additional plugins can be implemented at any time. smart/HUB can be expanded into a universal operator panel with a 7“ touch display. smart/HUB is part of the JES smart/architecture and serves both as an operator panel and as an IoT gateway for sensors without an Ethernet connection. The smart/architecture also includes smart/sensors and smart/CONTROL, a sensor control center for collecting and visualizing all sensor data, central user administration, sensor monitoring, and maintenance control and documentation. smart/HUB can be used wherever data from sensors from different manufacturers is to be collected and administered in a uniform form in one platform, e.B road weather stations, tunnel sensors. Advantanges
|
ApplicationTunnels are important infrastructure elements in road networks that facilitate connections between regions. The environmental conditions prevailing therein are influenced by smoke, fog, dust and exhaust gases and should be monitored so as not to expose people to dangers and impairments as they pass through. Fires in particular have had dramatic consequences in the past. At all times, people in the tunnel must be supplied with sufficient breathing air and suitable visibility conditions must be ensured. Since 1990, JES Elektrotechnik GmbH has been developing, installing and maintaining systems for monitoring air quality and lighting conditions in tunnels. Our systems are robust, durable and resistant to the corrosive tunnel atmosphere and work reliably and precisely. They comply with the requirements of Directive 2004/54/EC (minimum safety requirements for tunnels in the trans European road network) and the more precise national directives and regulations:
Our product range in the field of tunnel safety includes systems for measuring:
|
Technical Specifications
smart/HUB IoT Gateway, Data logger and Control unit
smart/HUB IoT Gateway, Data logger and Control unit with display
Accessories
smart/HUB-485 4 x RS-485 Extension
4 x RS-485 extension | |
---|---|
Type | smart/HUB-485 |
Power supply | via bus extender |
Field bus | 4 x RS-485 half-duplex (2-wire) |
Material | Polycarbonate (UL94 V-0) |
IP rating | IP 20 |
Dimensions | 17.8 x 89.7 x 60.7 mm |
Weight | 200 g |
Temperature range | -40 .. +60 °C |
Humidity range | 0 .. 100% relative humidity, non-condensing |
Pollution degree | 2 |