 t/FL-USP Air Flow Sensor


JES t/FL-USP Air Flow Sensor

Features

  • Precise ultrasonic air flow measuring system based on different transition times of ul-trasonic pulses
  • Measurement of airflow at a single point
  • Connection to tunnel control system either via analogue outputs or via RS 485 ASCII
  • Optional, remote smart/HUB touch operating unit to
    • display measured values
    • modify parameters
    • additional outputs

System setup

  • Single sensor for wall-mounting with system cable
  • t/FL-USP-TBX Terminal box for analogue and RS-485 connections
  • Alternative smart/BOX-S-FL-USP Terminal box for t/FL-USP air flow sensor with JES smart/CORE IoT gateway and operating unit
  • Optional smart/HUB touch operating unit

Operation

The air flow monitoring system measures the air flow based on different transmission times of ultrasonic pulses sent in one or the other direction.

The arms of this single point air flow sensor are directed in the longitudinal axis of the tunnel. Ultrasonic pulses are exchanged between the two sensor arms.

Air flow in the tunnel influences the transition time of the pulses between sender and receiver. Based on the difference in transition times of ultrasonic pulses sent in one or the other direction the measured values are calculated.

Measured values are air speed, air flow rate, direction of air flow and air temperature

Advantanges

  • Specifically developed for application in tunnels
  • No control unit required
  • Easy configuration
  • Corrosion resistant against aggressive tunnel atmosphere
  • Sensors can be replaced quickly with no tools and no re-alignment required
  • Minimised spare requirements
  • Extremely low maintenance requirements

Application

Tunnels are important infrastructure elements in road networks and facilitate the connection of regions.

Environmental conditions in tunnels are influenced by fog, particles and emissions and need to be monitored to protect people on their passage through the tunnel from danger and impacts on their health. Accidents in tunnels, and particularly fires, can have dramatic consequences and can prove extremely costly in terms of human life, increased congestion, pollution and repair costs. At every time people in the tunnel need to be supplied with breathable air and sufficient visibility.

Since 1990 JES Elektrotechnik GmbH develops, installs and maintains systems to monitor air characteristics and lighting conditions in tunnels. Our systems are robust, durable and resistant against the corrosive atmosphere in a tunnel. They operate reliably and have a high accuracy in measurement.

All systems fulfil the requirements of the EC guideline 2004/54/EC (Minimum safety requirements for tunnels in the trans-European road network) and the more detailed national guidelines and provisions:

  • Austria: RVS 09.02 Tunnelausrüstung
  • Germany: RABT Richtlinien für die Ausstattung und den Betrieb von Straßentunneln
  • Switzerland: ASTRA Richtlinien und Fachhandbuch Betriebs- und Sicherheitsausrüstungen (BSA)

Our range of products for tunnel covers systems for monitoring of

  • Visibility (extractive or in-situ)
  • Toxic gases like CO, NO, NO2 (extractive or in-situ)
  • Air velocity, direction and temperature
  • Luminance (access, threshold and interior zone)
  • Illuminance


Technical Specifications

Air flow measurement
Type JES t/FL-USX
Measuring method Determination of direction dependant differential transi-tion times of ultrasonic pulses
Measured values Air speed
Air flow rate
Direction of air flow
Air temperature
Measuring range -40 .. 40 m/s
Resolution 0.1 m/s, accuracy depending on measuring distance, flow profile, installation, typically <±0.2 m/s at 3 m/s
Response time > 1s … 180 s, configurable
Measurement path length 1.2 - 25 m
Alignment 30 - 60° to tunnel longitudinal axis, typically 45°

Outputs
Analogue output 1 x 4-20 mA, 400 Ω, isolated
can be assigned any measured value and output range
Output range configurable, typically: -20 to 20 m/s
Relay contacts 1 x fault indication (NC)
1 x direction of air flow (NC)
(max. 48 V / 0.5 A)
Digital interfaces 1x RS 485 MODBUS RTU to control system, bidirectional
1x Intercom RS 485 master-slave


Ultrasonic transceiver (sensor)

Sensor
Type DURAG D-FL 220T M
Operating voltage 24 VDC ± 10 %
Current consumption 1 A
Appliance class Class III
Service interface USB 1.1
MTBF > 170.000 h within service life if used within specifications
Material Sensor housing: Polyamide RAL5017, Flammability rating: B1 (UL 94 V0)
Wall bracket: Stainless steel 1.4404 (AISI 316L) or 1.4571 (AISI 316Ti)
IP rating IP 69
Dimensions 270 x 130 x 95 mm
Weight Sensor 2.2 kg
Wall bracket 1.6 kg
Indoor/Outdoor use Indoor use (tunnel)
Altitude up to 2,000 m
Temperature range -40 .. +70 °C
Humidity range 0 .. 100% relative humidity (non-condensing)
Pollution degree 4 (intended environment)


t/FL-USX-TBX terminal boxes

Terminal box A - JES t/FL-USX-TBX-A
Type t/FL-USX-TBX-A
System cable port 1 (for D-FL 220 T M Sensor A)
Power supply 100 to 240 VAC, 50/60 Hz
Supply voltage fluctuations ± 10 %
Overvoltage category II
Power rating 60 W
Appliance class Class I
Material Stainless steel 1.4404 (AISI 316L)
Mounting incl. mounting clamp made from Stainless steel 1.4404 for wall mounting
IP rating IP 69
Dimensions 250 x 160 x 110 mm
Weight approx. 3.2 kg
Indoor/Outdoor use Indoor use (tunnel)
Altitude up to 2,000 m
Temperature range -40 .. +60 °C
Humidity range 0 .. 100% relative humidity (non-condensing)
Pollution degree 4 (intended environment) / 2 (when cover removed)

Terminal box B - t/FL-USX-TBX-B
Type t/FL-USX-TBX-B
System cable port 1 (for D-FL 220 T M Sensor B)
Power supply 24 VDC ±10 %
Current rating 1 A
Appliance class Class III
Material Stainless steel 1.4404 (AISI 316L)
Mounting incl. mounting clamp made from Stainless steel 1.4404 for wall mounting
IP rating IP 69
Dimensions 160 x 160 x 110 mm
Weight approx. 1.9 kg
Indoor/Outdoor use Indoor use (tunnel)
Temperature range -40 .. +60 °C
Humidity range 0 .. 100% relative humidity (non-condensing)
Pollution degree 4 (intended environment) / 2 (when cover removed)


smart/BOX-S-FL-USX gateway (instead of t/FL-USX-TBX-A for Ethernet connection)

smart/Architecture gateway for t/FL-USX - smart/BOX-S-FL-USX
Type smart/BOX-S-FL-USX
System cable port 1 (for D-FL 220 T M sensor)
Power supply 100 to 240 VAC, 50/60 Hz
Supply voltage fluctuations ± 10 %
Overvoltage category II
Power rating 60 W
Appliance class Class I
Digital interfaces MODBUS RTU (RS-485)
MODBUS/TCP (Ethernet)
Webserver for configuration (Ethernet)
Material Stainless steel 1.4404 (AISI 316L)
Mounting incl. mounting clamp made from Stainless steel 1.4404 for wall mounting
IP rating IP 69
Dimensions 250 x 160 x 110 mm
Weight approx. 3.2 kg
Indoor/Outdoor use Indoor use (tunnel)
Altitude up to 2,000 m
Temperature range -40 .. +60 °C
Humidity range 0 .. 100% relative humidity (non-condensing)
Pollution degree 4 (intended environment) / 2 (when cover removed)

Conformities

Conformities
Markings
Electrical standards 2014/35/EU Low Voltage Directive (LVD)
2014/30/EU Electromagnetic compatibility (EMC)
EN 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use
EN 61326-1 Electrical equipment for measurement, control and laboratory use - EMC requirements
Tunnel safety standards AT: RVS 09.02.22
DE: RABT 2006
CH: ASTRA RL 13001, Fachhandbuch BSA
NO: Norwegian Public Roads Administration Handbook No. 021 Road Tunnels