User Tools

Site Tools


en:datasheets:tfl-usx
This is an old revision of the document. It contains one or more snippets which may be outdated.
Replace outdated snippets in this Old Revision?Yes No


 t/FL-USX Air Flow Monitoring System

JES t/FL-USX Air Flow Monitoring System

6.1 Technical data t/FL-USX system

Air flow measurement
Type JES t/FL-USX
Measuring method Determination of direction dependant differential transi-tion times of ultrasonic pulses
Measured values Air speed
Air flow rate
Direction of air flow
Air temperature
Measuring range -40 .. 40 m/s
Resolution 0.1 m/s, accuracy depending on measuring distance, flow profile, installation, typically <±0.2 m/s at 3 m/s
Response time > 1s … 180 s, configurable
Measurement path length 1.2 - 25 m
Alignment 30 - 60° to tunnel longitudinal axis, typically 45°

Outputs
Analogue output 1 x 4-20 mA, 400 Ω, isolated
can be assigned any measured value and output range
Output range configurable, typically: -20 to 20 m/s
Relay contacts 1 x fault indication (NC)
1 x direction of air flow (NC)
(max. 48 V / 0.5 A)
Digital interfaces 1x RS 485 MODBUS RTU to control system, bidirectional
1x Intercom RS 485 master-slave

6.2 Technical data t/FL-USX-TBX terminal boxes

Terminal box A - JES t/FL-USX-TBX-A
Type t/FL-USX-TBX-A
System cable port 1 (for D-FL 220 T M Sensor A)
Power supply 100 to 240 VAC, 50/60 Hz
Supply voltage fluctuations ± 10 %
Overvoltage category II
Power rating 60 W
Appliance class Class I
Material Stainless steel 1.4404 (AISI 316L)
Mounting incl. mounting clamp made from Stainless steel 1.4404 for wall mounting
IP rating IP 69
Dimensions 250 x 160 x 110 mm
Weight approx. 3.2 kg
Indoor/Outdoor use Indoor use (tunnel)
Altitude up to 2,000 m
Temperature range -40 .. +60 °C
Humidity range 0 .. 100% relative humidity (non-condensing)
Pollution degree 4 (intended environment) / 2 (when cover removed)

Terminal box B - t/FL-USX-TBX-B
Type t/FL-USX-TBX-B
System cable port 1 (for D-FL 220 T M Sensor B)
Power supply 24 VDC ±10 %
Current rating 1 A
Appliance class Class III
Material Stainless steel 1.4404 (AISI 316L)
Mounting incl. mounting clamp made from Stainless steel 1.4404 for wall mounting
IP rating IP 69
Dimensions 160 x 160 x 110 mm
Weight approx. 1.9 kg
Indoor/Outdoor use Indoor use (tunnel)
Temperature range -40 .. +60 °C
Humidity range 0 .. 100% relative humidity (non-condensing)
Pollution degree 4 (intended environment) / 2 (when cover removed)

6.3 Technical data D−FL 220T M measurement sensor

Sensor
Type DURAG D-FL 220T M
Operating voltage 24 VDC ± 10 %
Current consumption 1 A
Appliance class Class III
Service interface USB 1.1
MTBF > 170.000 h within service life if used within specifications
Material Sensor housing: Polyamide RAL5017, Flammability rating: B1 (UL 94 V0)
Wall bracket: Stainless steel 1.4404 (AISI 316L) or 1.4571 (AISI 316Ti)
IP rating IP 69
Dimensions 270 x 130 x 95 mm
Weight Sensor 2.2 kg
Wall bracket 1.6 kg
Indoor/Outdoor use Indoor use (tunnel)
Altitude up to 2,000 m
Temperature range -40 .. +70 °C
Humidity range 0 .. 100% relative humidity (non-condensing)
Pollution degree 4 (intended environment)

6.4 Technical data smart/BOX-S-FL-USX gateway (additional)

smart/Architecture gateway for t/FL-USX - smart/BOX-S-FL-USX
Type smart/BOX-S-FL-USX
System cable port 1 (for D-FL 220 T M sensor)
Power supply 100 to 240 VAC, 50/60 Hz
Supply voltage fluctuations ± 10 %
Overvoltage category II
Power rating 60 W
Appliance class Class I
Digital interfaces MODBUS RTU (RS-485)
MODBUS/TCP (Ethernet)
Webserver for configuration (Ethernet)
Material Stainless steel 1.4404 (AISI 316L)
Mounting incl. mounting clamp made from Stainless steel 1.4404 for wall mounting
IP rating IP 69
Dimensions 250 x 160 x 110 mm
Weight approx. 3.2 kg
Indoor/Outdoor use Indoor use (tunnel)
Altitude up to 2,000 m
Temperature range -40 .. +60 °C
Humidity range 0 .. 100% relative humidity (non-condensing)
Pollution degree 4 (intended environment) / 2 (when cover removed)


7 Standards and regulations

The DURAG GROUP is certified to ISO 9001. The products are manufactured to national, European and international standards.

Conformities
Markings
Electrical standards 2014/35/EU Low Voltage Directive (LVD)
2014/30/EU Electromagnetic compatibility (EMC)
EN 61010-1 Safety requirements for electrical equipment for measurement, control and laboratory use
EN 61326-1 Electrical equipment for measurement, control and laboratory use - EMC requirements
Tunnel safety standards AT: RVS 09.02.22
DE: RABT 2006
CH: ASTRA RL 13001, Fachhandbuch BSA
NO: Norwegian Public Roads Administration Handbook No. 021 Road Tunnels

en/datasheets/tfl-usx.1709155454.txt.gz · Last modified: by jesadmin